Navigation:

EMS Outputs > 3rd Party Equipment Control (MS1000) > Conset  >> Control Setup (Conset)

Control Setup (Conset)

EMS's Control Setup (Conset) functionality is designed to allow the configuration of inputs to and outputs from CR3 (CR3 NW) Control Receivers.

Outputs from CR3 (CR3 NW) Control Receivers can be used to trigger the operation of 3rd party control devices (e.g. motorised heating System valves), either directly or via MS1000 Control Units.

Conset  is only used for configuring the Control Settings for CR3 (CR3 NW) Control Receivers.

Once configured, a CR3 (CR3 NW) is autonomous, requiring no external software or network connection to operate, though a network connection will be initially required to allow Conset to connect to the CR3 (CR3 NW) Controller and configure it.

Note:Conset in EMS cannot be used to configure legacy CR3 controllers, these must be upgraded to CR3 controller to enable control from EMS; please contact your Local Distributor or Hanwell Sales for details.

Example Application

Accessing Conset Functionality

Control Settings

Accessing Conset Functionality

Click here for details on Accessing Conset Functionality if you are using a version of EMS prior to Version 1.0.9 / 2.0.3 (Compliant)

Conset functionality is accessed from within EMS as follows:

1.From the SETTINGS entry in the System drop-down menu, select Conset Setting. See Figure 1371 below:

Figure 1371

Conset Setup System Menu2

 

2.The View Conset Groups window is displayed, showing only CR3 (CR3 NW) Control Device Groups available for configuration by the Conset application via the [Control System Settings], [Control Sensors Settings] and [Mixer Settings] functions.
See Figure 1372 below:

Figure <%HMFIGURECOUNTER%>

Conset index2

If no CR3 (CR3 NW) Control Device Groups are available, the following window is displayed and you will need to add/define the required CR3 (CR3 NW) Control Device Groups. See Figure 1372 below:

Figure 1372

View Conset Groups No Device Group Available2

Control Settings

There are three types of setting available to a Conservation Heating Scheme in EMS to enable it to maintain the ambient Relative Humidity (RH) of an area at the desired %RH Setpoint (+/- the RH Hysterisis Setting) through the use of temperature modulated control:

Control System Settings

Covers the settings that will be the same for all Sensors (for example, house Opening Time and Closing Time).

Control Sensor Settings

Covers the settings of each individual Sensor and includes parameters such as the %RH Setpoint.

Mixer Settings

In wet heating Systems where there is a primary boiler loop feeding into secondary heating circuits, the EMS System's outputs can contribute to maintaining the ambient RH by adjusting the position of the heating installation's mixer valve according to a Proportional-Integral (PI) algorithm using the K and I values set for the control channel via Conset.

Adding or Editing Control System Settings for a Device/Control Group

1.Cick on [Control System Settings] adjacent to the required Control Group's entry in the View Conset Groups window.

The Control System Settings window is displayed for the selected Device/Control Group. See Figure 1373 below:

Figure 1373

Conset Edit Control Settings3

2.Click on Edit.

The Edit Control System Details window is displayed with the Control System Details fields activated, allowing values to be entered. See Figure 1374 below:

Figure 1374

Conset Edit Control Settings4

3.Edit the Control System Details as required.

Note:

Only Day and Month values are used by CR3s; the Year value in any setting merely facilitates the use of the Date-Time Picker controls, the Year value is not sent to the CR3.
As a consequence of this, Year values can be set to any year, but will automatically roll over to following years.

  Click on the Save Changes button. See Figure 1374 above.

The edited Control System Details are saved and you are returned to the View Conset Groups window which displays a Control System updated successfully message. See Figure 1375 below:

Figure 1375

Control System Updated Successfully2

5.Click on the Back button to return to the Control System Settings window.

Adding or Editing Control Sensor Settings for a Device/Control Group

Click on [Control Sensors Settings] adjacent to the required Control Group's entry in the View Conset Groups window.

The Control Sensor Settings [Device/Control Group Name] window for the selected Device/Control Group is displayed. See Figures 1376 below:

Figure 1376

Conset Control Sensor Window No Sensors Added2

From this window you can:

Add a Control Sensor

Delete a Control Sensor

Edit a Control Sensor's Parameters

To Add a Control Sensor to the Control Group:

1.In the Control Sensor Settings window, click on the Add Sensor button.

The Add Sensor window for the selected Control Group is displayed. See Figure 1377 below:

Figure 1377

Conset Add Control Sensor2

2.Select a Sensor to use as a Control Sensor from the Sensor Name drop-down list in the Hardware and Set Points pane.

To add a new Sensor to the CR3(CR3 NW) Control Group and thereby make it available in the Sensor Name drop-down list, refer to: Add/Assign Sensors to a Zone and Associating a Sensor with a CR3/CR3 (NW) Control Device.

3.If necessary, edit the required Control Sensor Parameter values for the selected Control Sensor.

Click on the panes in Figure 1377 above to show details of each Control Sensor Parameter.

4.When all required changes have been completed, click on the Add Sensor button.

A Control Sensor Settings window is displayed showing the new Control Sensor and a confirmation message. See Figure 1378 below:

Figure 1378

Control Sensor Added Successfully

To Delete a Control Sensor from the Control Group:

In the Control Sensor Settings window, click on [Delete] in the Actions column on the row containing the Control Sensor to be deleted. See Figure 1379 below:

Figure 1379

Conset Control Sensor Index 2

The selected Control Sensor is deleted.

To Edit a Control Sensor's Parameters:

1.In the Control Sensor Settings window, click on [Edit] in the Actions column on the row containing the Control Sensor to be edited. See Figure 1380 below:

Figure 1380

Conset Control Sensor Index 3

Control Sensor Settings window is displayed for the selected Sensor, showing the same Control Sensor parameters, as displayed in the Add Sensor window above, and populated with the selected Control Sensor's parameter values. See Figure 1381:

Figure 1381

Conset Add Control Sensor2

2.Edit the selected Control Sensor's parameter values as required.

3.Click on the Save Changes button.

The new parameter values are saved and the Control Sensor window is displayed with a confirmation message. See Figure 1382 below:

Figure 1382

Control Sensor Updated Successfully

Control Sensor Parameters

Hardware and Set Points

Figure 1383

Hardware Set Points

Sensor Name

The name of the new/edited Sensor.

MS1000 Card Number

The card number of the MS1000 card controlled by the Sensor.

If the Sensor is not controlling any outputs, this value should be set to 0 (zero). When this value is set to 0, no settings will be displayed.

See Document Number: GD4619-1 MS1000 Control System Manual

MS1000 Channel Number

Defines the MS1000 Output Channel that the selected Sensor is controlling.

If the Sensor is not controlling any outputs, this should be set to 0 (zero). When this value is set to 0, no settings will be displayed.

Note: If transferring from a RadioLog System, Channel allocations will no longer be defined solely by a Channel Number but will, instead, be defined by the MS1000 Card Number and that Card's MS1000 Channel Number. See Figure 1383 above.
> See the table below for Channel numbering definitions in RadioLog compared to EMS:

RadioLog Channel Numbering

EMS Channel Numbering

RadioLog Channel Number

EMS Card Number

EMS Card Channel Number

1

Card 1

1

2

Card 1

2

3

Card 1

3

4

Card 1

4

5

Card 2

1

6

Card 2

2

7

Card 2

3

8

Card 2

4

9

Card 3

1

10

Card 3

2

11

Card 3

3

12

Card 3

4

13

Card 4

1

14

Card 4

2

15

Card 4

3

16

Card 4

4

Is Radio Connection

If the channel is controlled by radio transmissions from the CR3 (CR3 NW), the Is Radio Connection box should be checked.

If the selected Sensor is hardwired to the Control Unit, rather than communicating wirelessly, the Is Radio Connection box should be left unchecked.

Transmission Radio ID

The ID of the selected wireless Sensor.

Valid radio IDs are 1 to 254.

0 is used to represent radio off (no wireless connection).

Humidifier Control

Check the Humidifier Control box if the selected Sensor is controlling a Humidifier.

Lower Temperature

If this temperature is reached, the heating will automatically switch ON, regardless of the RH control requirements. This prevents under-heating or frost-damage of an area.

The default value is 15oC.

%RH Set Point

This is the %RH point at which the heating will be turned on to drive down humidity, irrespective of the Steward Temperature setting.

Minimum %RH

This setting overrides the Steward Temperature so that the RH never drops below the Minimum % RH set here. This is to prevent over-drying of an area.

The default value is 40%RH.

RH Hysteresis

This value represents the 'width'/sensitivity of the RH switching band.

For Example: If a Hysteresis of 1 is set and the RH Setpoint is 55 (%) then the System will turn a heater on at 56%RH and off at 54%RH.

Season Upper Temperature

If this Temperature value is reached during the Season dates/ times set in the Control System Settings [Control Group name], the heating will automatically switch off, regardless of the RH control requirements. This prevents the overheating of an area.

The default value is 22OC.

Out of Season Upper Temperature

If this Temperature value is reached outside the Season dates/ times set in the Control System Settings [Control Group name], the heating will automatically switch off, regardless of the RH control requirements. This prevents the overheating of an area.  

The default value is also 22OC.

Steward Temperature

This option allows a different Lower Temperature value to be set during opening hours, for human comfort, and can be specified as part of a Comfort Heating Scheme.

The software will use this setting during Opening Times/ Days (see the Site Details settings).

This value should be higher than the Lower Temperature setting.

The default value is 15OC.

Note:The, optional, Min % RH value overrides the Steward Temperature so that the Relative Humidity never drops below the Minimum % RH set here. This is to prevent over-drying of an area. The default value is 40% RH.

Domestic and Comfort Settings

It is possible to set temporary or permanent overrides of the optimum Conservation Heating settings - defined in the Hardware and Setpoints section - to create an optimum conservation environment to allow for events running outside standard opening hours or to accommodate offices or domestic areas.

It assumed that these rooms are cleared of objects of cultural value whist they are being used as an office or during the period that the special event is occurring and, as a result, the Minimum %RH setting can be safely ignored.

If there are item of cultural value in the rooms used for offices or events, then the Use Minimum %RH box can be selected and heating will be reduced where humidity is too low.

During the periods that Domestic and Comfort settings are active, the System will try to maintain the temperature set in the Domestic and Comfort Settings section of the Control System Settings [Control Group name] window.

If these parameters are enabled , by checking the Comfort Configuration Enabled box, the selected Sensors will then be activated for Comfort Heating within the set time span. See Figure 1384 below:

Figure 1384

Domestic and Comfort Settings

Comfort Configuration Enabled

Ticking this box allows the setting of permanent or temporary overrides to conservation-optimum temperature settings.

Use Minimum %RH

If this Minimum %RH value is reached during the Season dates/ times set in the Opening Hours Edit/View Control System window, the heating will automatically switch off, regardless of the RH control requirements. This prevents the overheating of an area.

Temperature

Defines the Comfort/Steward Temperature.

Comfort Start Date

Start date of the Comfort Temperature override of the Conservation Heating settings.

Comfort End Date

End date of the Comfort Temperature override of the Conservation Heating settings.

Comfort Start Time

Start time of the Comfort Temperature override of the Conservation Heating settings.

Comfort End Time

End time of the Comfort Temperature override of the Conservation Heating settings.

Note:

Only Day and Month values are used by CR3s; the Year value in any setting merely facilitates the use of the Date-Time Picker controls, the Year value is not sent to the CR3.
As a consequence of this, Year values can be set to any year, but will automatically roll over to following years.

Domestic Days

If the Comfort override is being used to control an office or domestic area, tick the Domestic Enabled box and then select the relevant Domestic Days by ticking the appropriate boxes. The Comfort override will then operate between the Comfort Start Date and Comfort End Date on these days of the week for all future weeks. See Figure 1385 below:

No date settings are required in this case.

Figure 1385

Domestic Days Interface

 

Domestic and Comfort Settings - Examples:

One Off Special Event

For a one-off special event, such as a party or wedding etc. the Comfort Settings can be used.

1.Set the required temperature; the Start and End dates and the Start and End times for the event in the Domestic and Comfort Settings section.

2.Check that Use Minimum %RH is correctly selected (if necessary), select Comfort Configuration Enabled and deselect Domestic Enabled in the Domestic Days section.

Office or Domestic Areas

For office or domestic areas that are regularly occupied, perhaps on certain days, the Domestic Days settings can be used. In these area temperature control overrides RH control most of the time.

1.Set the required temperature and the Start and End times between which the room will be occupied.

Note:For 24 hour occupation, set 00:00 to 23:59.

2.Check that Use Minimum %RH is blanked (normally) and deselect Comfort Configuration Enabled.

3.In the Domestic Days section, select the days of the week that the room will be occupied and then select Domestic Enabled.

Secondary Loop Settings

Normally these settings will be setup on commissioning  and left as-is during normal operation.

The Secondary Loop settings provided in this window can be used to provide proportional control of a wet heating System.

Control is provided by either a variable voltage, or 4 to 20mA, signal from an MS1000 Analogue card, the signal being used to control the opening and closing of a motorised valve controlling the loop flow, usually to one or more radiators.

The MS1000 card and its output are defined by setting the Wet Mixer Card Number and Wet Mixer Channel fields.

PID Controller - K & I Constants

Use of Proportional Control in Heating Control

For most heating control Systems, the rate of change is slow and on/off relay control will provide effective control, without the need for proportional control outputs and valves.

Where Proportional Control is required then, from experience, it has been found that values of around 100 for K generally work best. I generally has very little effect on control - again due to the naturally slow rate of change in heating Systems - and can generally be left at 0.

To use these controls, select the In Loop heater check box setting. See Figure 1386 below:

Figure 1386

Conset Secondary Loop Settings

In Loop Heater

If the target device is a wet radiator (rather than electric) then this box should be checked.

This is used to generate the Boiler demand signal.

Control Constant (Proportional K)

This setting adjusts the proportional control's Controller Gain (Kc); a higher controller gain increasing the amount of proportional control action for a given error.

If the controller gain is set too high the control loop will begin oscillating and become unstable.

If the controller gain is set too low, it will not respond adequately to disturbances or Set Point changes.

The Proportional Control Constant is the main parameter determining ongoing humidity control.

Control Constant (Integral I)

This setting (the integral term) increases action in relation not only to the error but also the time for which it has persisted. So, if the applied force is not enough to bring the error to zero, this force will be increased as time passes.

The Integral Control Constant refines ongoing humidity control towards zero static error.

Note:If the output channel is an analogue card controlling a mixer valve in a wet heating System then the K and I coefficients of the PI control algorithm are set here, otherwise they MUST be left at 0.

Wet Mixer Card Number
Wet Mixer Channel

These values are used to control a motorised valve to generate a constant temperature secondary loop.

The Wet Mixer Card Number and Wet Mixer Channel fields define the analogue output (Card Number and Channel Number respectively) that controls the motorised valve on the loop associated with that Sensor.

See Control Mixer Sensor Settings.

Accessing Mixer Settings for a Control Device Group

The following sections cover more advanced heating control parameters; these should be configured by a Hanwell Engineer, in association with your Heating Contractor.

To Access Mixer Settings for a Control Device Group:

Click on [Mixer Settings] adjacent to the required Control Device Group's entry in the View Conset Groups window.

The Mixer Settings [Device/Control Group Name] window is displayed for the selected Control Device Group. See Figure 1387 below:

Figure 1387

Conset Mixer Settings NEW

From this window you can:

Add a Control Mixer

Return to the View Conset Groups Window

Edit the Mixer System Details

Edit/Delete a Control Mixer Sensor

To Add a Control Mixer:

1.In the Mixer System Details window, click on the Add New Mixer button.

The Add New Mixer window is displayed. See Figure 1388 below:

Figure 1388

Conset Add Control Mixer NEW

2.Select the Control Mixer parameters' values from the relevant drop-down lists/up-down arrows:

Temperature Sensor

The ID and name of the Sensor controlling the Secondary Loop.

Temperature Sensor Channel

The channel of the Temperature Sensor on this loop.

Humidity Sensor

The ID of the room Sensor controlling this loop.  

Mixer Card

The ID of the MS1000 output card controlling this mixer (1 - 253).

Mixer Channel

The channel of the MS1000 output card controlling this mixer (1 - 4).

Pump Card

The ID of the MS1000 output card controlling the associated pump (1 - 253).

Pump Channel

The channel of the MS1000 output card controlling the associated pump (1 - 4).

Maximum Temperature

The maximum permitted secondary flow temperature (OC).

Tick the check box in the Global column if the value set for the Maximum Temperature is to apply to all Sensors in the Control Group.

Overrun Time

The time in minutes the pump should overrun after mixer valve closure.

Tick the check box in the Global column if the value set for the Overrun Time is to apply to all Sensors in the Control Group.

3.Click on the Add Mixer button.

The new Mixer is added, the Add New Mixer window returns to a state facilitating the addition of further Mixers and a Control Mixer added successfully message is displayed. See Figure 1389 below:

Figure 1389

Control Mixer Added Successfully NEW

To Return to the View Conset Groups window:

Click on View Conset Groups on the main menu bar. See Figure 1390 below:

Figure 1390

Return to View Conset Groups

To Edit the Mixer System Details:

1.In the Mixer System Details section of the Mixer Settings [Control Device Group name] window, click on the Edit button.

The Edit Mixer window is displayed . See Figure 1391 below:

Figure 1391

Edit Mixer System Details

2.Edit the Mixer System Details:

Boiler Demand Card

Low Ghost Sensor Physical ID

High Ghost Sensor Physical ID

3.Click on Save Changes.

You are returned to the Mixer Settings [Control Device Group name] window displaying a message stating: 'Control Mixer System updated successfully'.  See Figure 1392 below:

Figure 1392

Control Mixer Added Successfully NEW2

To Edit/Delete a Control Mixer Sensor:

To Edit a Control Mixer Sensor

To Delete a Control Mixer Sensor

To Edit a Control Mixer Sensor

1.In the Sensor Name(s) section of the Mixer Settings [Control Device Group name] window, click on the [Edit] link on the row containing the Control Mixer Sensor to be edited/deleted. See Figure 1392

The Edit Mixer [Control Device Group name] window is displayed.  See Figure 1393:

Figure 1393

Edit Mixer NEW

2.Select the required  parameter values for the selected Control Mixer Sensor from the relevant drop-down lists/up-down arrows.

3.Click on the Update Mixer button.

You are returned to the Mixer Settings [Control Device Group name] window displaying a Control Mixer updated successfully message. See Figure 1394 below:

Figure 1394

Control Mixer Updated Successfully NEW

To Delete a Control Mixer Sensor

1.In the Actions column of the Sensor Name(s) section of the Mixer Settings [Control Device Group name] window , click on [Delete] in the row containing the Sensor to be deleted. See Figure 1394 above.

2.Click on Yes in the displayed warning window. See Figure 1395 below:

Figure 1395

Delete Selected Mixer Yes-No

The selected Control Mixer Sensor is deleted.