This feature allows you to enter Notes relating to a Sensor/Transmitter's Alarm.

Alarm Notes are especially useful for inexperienced operators, giving them instructions on what to do when an Alarm occurs.

For example:In the middle of the night the temperature increases in a room or space containing high value objects and an Alarm is generated. The night shift operative or security guard will be presented with the Alarm Note which states:
On a high temperature alarm contact facilities on Ext 235 and report the alarm condition and the room location”.

The System can be set up so that low level Users can monitor the System and respond to alarms, but can’t make changes.

This feature means that someone not familiar with an area or its contents can still effectively and efficiently deal with an alarm condition.

Accessing and Editing Alarm Notes

To Access the Alarm Notes for a Sensor/Transmitter's Alarm:

1.From the required Site's Live View window, select Edit Mode from the main View Data menu. See Figure 916 below:

Figure 916

Edit Zone Entry View Data Drop Down Menu

Click here for details on Alarm Notes if you are using a version of EMS prior to Version 1.0.9 / 2.0.3 (Compliant)

The Site's Edit Mode window is displayed. See Figure 922 below:

Figure 922

Edit Mode Window

By default, the Sensor and Zone editing/configuration window for the Zone at the top of the left-hand menu is displayed.

To display another Zone's Edit Mode window, click on the entry for the required Zone in the left-hand menu. For an example, see Figure 923 below:

Figure 923

Change Zone2

2.Either:

i.In the left-hand list of the Zone's Edit Mode window, click on the small 'arrow' symbol to display a list of the Sensors associated with the Zone. See Figure 924 below:

Figure 924

Zone Sensor Arrow Symbol

 

ii.In the left-hand list, click on the required Sensor's icon Sensor Icon.

Or:

In table in the Zone's Edit Mode window, click on the required Sensor's name in the Sensor Name column. See Figure 925 below:

Figure 925

Select Sensor Name Edit Mode Table

The Edit Mode window for the selected Sensor is displayed.  See Figure 926 below:

Figure 926

Edit Mode Window for Sensor

3.Click on the ALARMS pane at the bottom of the Edit Mode window to access the Alarm Parameter/Level functionality.  See Figure 926 above.

The ALARMS pane is displayed. See Figure 927 below:

Figure 927

Sensor Properties Alarms

4.Click on the Alarm Notes tab to display the Alarm Notes pane for the selected Sensor/Transmitter. See Figure 928 below:

Figure 928

Alarm Note Window

5.Type your Sensor/Transmitter's Alarm Note into the Alarm Notes dialog box or edit an existing Alarm Note.

6.When happy, click Save. See Figure 928 above.

This will save the Alarm Note and either associate the Note with, or update the existing Note of, the currently selected Sensor/Transmitter.

If the Update has been successful, you will be returned to the Zone's Edit Mode window and the following message will be displayed. See 929 below:

Figure 929

Calibration Default Values OK

 

Individual Alarm Notes can be assigned for every Sensor/Transmitter on the System.